Material | Elastomer |
Working Temperature | -10 to 55 Deg C |
Thickness | 2.0 mm, 2.5 mm, 3.0 mm |
Tensile Strength | 15 N/mm2 |
Usage | Use for electronic workshop |
Layer | Three layers |
Class | A, B, C |
Voltage | 3.3 Kv, 11 Kv, 33 KV |
Dimension | 1 mtr * 2 mtr |
What is Electrical Rubber Mat?
Electrical rubber mats are an important health and safety product, often used in industrial applications to protect staff members from electric shocks. Electrical Rubber mat, sometimes referred to as an insulated floor covering helps protect individuals working on electrical installations from the dangers of electric shock. Electrical rubber Mat is a vital part of electrical safety and is typically used for protection around areas where high voltage equipment is being used.
What is Electrical Rubber mat used for?
An Electrical Rubber mat is a rubber floor covering which provides insulation in any standing area that puts you at risk of an electric shock. Where there is risk of shock, all industries require electrical rubber mat.
Electrical Rubber mat specification
Electrical rubber mats are required to offer certain levels of electrical protection, depending on the level of risk. The specifications of electrical rubber mat will depend on the voltage level. Generally, the larger the voltage, the higher the specification of electrical rubber mat needed. For example, if the working voltage is 450V, the electrical mat selected should be suitable. It is important, when choosing an electrical rubber mat for electrical safety, that the specification of the product is quantified, for example the 1000V electrical safety mat stocked at Laxmi Rubber Industries is specified as a BS EN 61111.
Why is Laxmi Rubber Industries the best supplier for Electrical Rubber Mat?
Laxmi Rubber Industries is a leading manufacturers and supplier of safety products, including electrical rubber mat. If you require electrical rubber mat, we are here to provide you the best solution at Laxmi Rubber Industries, where you will find a wide range of Electrical Rubber Mat suited to different voltages. Our electrical rubber mat is available in a range of sizes and can be made to order if required.
Laxmi Rubber Industries’ Electrical Rubber Mats are designed to comply with the latest Indian standards IS 15652:2006. This type of electrical rubber mat consists of technically advanced features and can withstand stringent industrial conditions with ease. Staff such as electricians, technicians, laborers, and workmen can be assured of enhanced safety with this type of electrical rubber mat. The electrical rubber mat is made up of elastomer which is a combination of rubber, elastomeric compounds, and PVC. The presence of anti-skid properties helps any sort of slippage while the electricians work atop these mats.
Features of LRI’s Electrical Rubber Mats briefly
- ISI Marked
- BIS Approved
- High Voltage Resistant
- Type Tested
Natural Rubber Sheet
Color | Black |
Thickness | 1 mm - 50 mm |
Density | 1.5~2.0 g/cm3 |
Material | Natural Rubber |
Packaging Type | Roll |
Temperature Range | -60 C~ to +260 C |
Electrical Safety Rubber Mats
Thickness | 2.0 mm, 2.5 mm, 3.0 mm |
Working Temperature | -10 to 55 Deg C |
Tensile Strength | 15 N/mm2 |
Brand | Laxmi Rubber |
Voltage | 3.3 Kv, 11 Kv, 33 KV |
Dimension | 1 mtr * 2 mtr |
Features:
- The electrical mats are a per new ISI
- These are also popularly known as rubber insulating mats
- Sizes available are 1x2 mtrs,1x5mtrs and 1x10 metres
- Available in 2.00mm, 2.5mm and 3.00 mm
- Material Test certificates for the same will be provided
Electrical Insulation Rubber Mat
Brand | Laxmi Rubber |
Thickness | 2 /3 /4 mm |
Material | Elastomer |
Working Temperature | -10 to 55 Deg C |
Tensile Strength | 15 N/mm2 |
Form | Rolls/Mat |
Roll length | 20m,45m,90m |
Features:
- Highly appreciated
- Fine finish
- Best quality
- Longer life
Poly Electro Safe Mat
Color | Any Color but without Metallic Derivatives |
Material | Elastomer |
Working Temperature | -10 to 55 Deg C |
Size/Dimension | 1mtr x 2mtr |
Tensile Strength | 15 N/mm2 |
Voltage | 3.3 Kv, 11 Kv, 33 KV |
- High Voltage Panels
- Sub-station
- Power Transformer Rooms
- LT HT Labs
- Near Bus bars
- Near Control Panels etc.
Technique Specifications:
Voltage Ratings:
- Class Thickness Grade KV Proof voltage B/Down voltage
- A 2.0 mm 3.3 10KV/3 minutes 30 KV
- B 2.5 mm 11 22KV/3 minutes 45 KV
- C 3.0 mm 33 36KV/3 minutes 65 KV
Construction:
- Made from Highly Electrical resistant Elastomers, free from any insertions (includes rubbers, latex and Elastomeric compound that may be natural or synthetic or a mixture or a combination of both)
- Surface: Upper surface of the mat is having small anti-skid aberration marks (rough surface, without edges) to avoid slippery effects and lower surface is plain.
Dimensions:
- Sizes are 1mtr x 2mtr or long length and thickness as per classification designation
Color:
- Any Color but without Metallic Derivatives.
Working Temp:
- -10 to 55°C
Typical Features:
- Confirming IS: 15652/2006 (Latest), ISI marked.
- High Die Electric Strength Up to 65 KV.
- Insulation Resistance Up to 1494000 Mega Ohm.
- Fire Retardant.
- Good Mechanical Properties to with Stand Load and Movement of Breaker Trolleys and Associated Electrical Equipment including heavy foot traffic.
- No Adverse Effect of Acids, Alkalis and Transformer Oil.
- Manufactured Without Any Metallic Derivatives
- Suitable For Both A.C D.C Electrical Installations
- Easy To Install, Can Be Pasted.
- Water And Moisture Proof, Does Not Decay.
- High Tensile Strength and Elongation Properties.
Additional Information:
- Item Code: IS-15652-2006
Electrical Insulation Anti Skid Rubber Mat
Thickness | 2.0 mm, 2.5 mm, 3.0 mm |
Material | Elastomer |
Type | Electrical Insulating Mats, Electrical Rubber Mats |
Voltage | 3.3 Kv, 11 Kv, 33 KV |
Dimension | 1 mtr * 2 mtr |
Working Temperature | -10 to 55 Deg C |
Tensile Strength | 15 N/mm2 |
- Safety Insulation Mats as per IS:15652, with the view of technical advancement & more stringent Industrial safety parameters.
- Insulating mats safeguard life of Electricians & other Technicians, in case of any accidental current leakage while working on AC or DC installations.
- Synthetic Insulation mat confirms complete safety of workers handling Live electronic equipments.